Browse our other Steam Boilers
Boiler Specifications:Boiler OutputBoiler Type - Multiple water tube, once through, forced flow, steam boilerMaximum Allowable Working Pressure PSIG 170Recommended Operational Range PSIG 70 - 150Boiler Heating Surface Area ft2 196Boiler Horsepower Rating BHP 100Equivalent Output in lb/hr 3,450Maximum Heat Output MMBTU/hr 3.348Turn-Down - 2:1 (50%)Air and Fuel Requirements (Natural Gas/Propane)Fuel Supply Pressure PSIG 3-5 PSIG (Natural Gas or Propane)Heat Input MMBTU/hr 3.939Efficiencyii % 85%Flue Gas Excess Oxygen % 5.0%Flue Gas Temperatureii °F 270NG/LPG Fuel Consumptioniii SCFH / GPH 3,860 / 43.0Required Air Volume SCFH 48,730Flue Gas Volume - Wet SCFH 52,590Flue Gas Volume - Dryiv SCFH 45,100Flue Gas Velocity ft/s 19.8Emissions (Natural Gas/Propane)NOx Emission NG/LPGvii ppm (lbs/MMBTU) 100/130 (0.1217 / 0.1582)CO Emission NG&LPGvii ppm (lbs/MMBTU) 100 (0.0739)CO2 Emission NG/LPGvii lbs/MMBTU 117.6 / 136.6VOC Emission NG&LPGvii lbs/MMBTU 0.0054SO2 Emission NG/LPGviii lbs/MMBTU 0.00058 / 0.00055Total PM Emission NG/LPGvii lbs/MMBTU 0.0075 / 0.0077Weights & CapacitiesBoiler Shipping Weight lbs 4,600Economizer Shipping Weight lbs 700Operational Weight lbs 5,900Operational Water Contentxi Gal 65Fully Flooded Water Contentxii Gal 120Along with the boiler comes a fully functional CSA certified blow down tank and a boiler feed water tank.Additional Prep Fees May Apply