Specifications below were provided from Frick when the unit was new. There may have been modifications that we are unaware of since this is used machinery. Frick 6-Fan Evaporative Condenser. 10845.50 MBH based on 95.00°F condensing temp. with an entering air wet bulb of 78.00°F. Refrigerant: R-717.
Fan Motor(s): Six (6) 10 HP fan motor(s): Totally Enclosed, Fan Cooled (TEFC),
1 Speed/1 Winding - Premium Efficiency (Inverter Duty), suitable for 460 volt, 3 phase,
60 hertz electrical service. Drives are based on 0 inches ESP.
NOTE: Inverter Duty fan motors, furnished in accordance with NEMA Standard Mg.1 -- Part 31, are required for applications using variable frequency
drives for fan motor control.
Pump(s): Two (2) 7.5 HP pump motor: 1 Speed/1 Winding, suitable for 460 volt, 3 phase, 60 hertz.
Fan housings may need repair.
May not have all Catwalk that was around the unit during installation.